-19-
Fig. 6.
7
Fit the loose pump grommet in the kit onto the hose (supplied as part of the unit) at the electrics end (Fig. 6).
8
Push the hose (referred to in 7) fully onto the condensate pump outlet and secure as far onto the outlet as possible
with the 4" cable tie (Figs. 6 and 7).
9
Secure the green/yellow cable and pump support wire to the coil hanger bracket with No. 8 screws (Fig. 6).
10
Push the grommets on the hose into the pump support wire; the arrows on the pump must point towards the motor
(Fig. 6).
Fig. 7.
11
The sensor/filter assembly is supplied fitted to a transition bracket.
a
If the unit has been supplied with a sensor bracket fitted, align the holes in the transition bracket with those in
the sensor bracket and connect together with the No. 6 screws (Fig. 7).
b
If the unit has been supplied without a sensor bracket fitted, disengage the sensor from the transition bracket,
align the holes in the transition bracket with those in the coil hanger bracket and secure together using the No.
8 screws. Refit the sensor to the bracket (Fig. 7).
12
Push the hose from the pump onto the sensor pick up spout (Fig. 7). Route the hose to avoid kinking.
13
Push the control board mounting feet into the four holes on the electrics plate (Fig. 6) and mount the control board.
14
Remove and discard the terminal covers from the black and blue wires, remove and retain the curly lok cable tie and
make the following connections to the control board (wiring diagram below)
.
a
Black cable to terminal L.
b
Blue cable to terminal N.
c
Pump cable to terminal PL
.
d
Pump cable to terminal PN
.
e
Sensor block flying lead plug to the six pin connector (CON 1)
.
f
Cut the looped red cable, (Fig. 6), bare back each half by 6mm and connect to the plug-in screw terminal block
TB1.
g
Use the curly lok cable tie to secure the wires and the sensor lead to the condensate outlet pipe above the
transformer.