58
de
fr
en
nl
Operating -
BrainCube control
menu
- Selected applications
:
page 65
:
page 68
manual switching
manual switching
activate | deactivate | test
:
page 57
last 20 messages
standard: de, en, fr, nl
:
page 59
Start-up
Check
Parameter
Info
Tightness
Check pumps/valves
Check outputs
Water make-up
View check
Type
Pleno PI .2
Version
V2.10
Min Pressure P0
1.8 bar
Initial pres. Pa
2.1 bar
Final pres. Pe
2.5 bar
NS sender BrainCube
1
View messages
View start-up
Language selection
Date
12.01.2007
Time
15:38
Stat. height HST
15 mWs
T limiter TAZ
<100°C
Safe. valve PSV
3.0 bar
Primary vessel
200 l
Water make-up quant.
Mode
fillsafe
Output 1
Output 2
Contrast
120
Start-up
Main menu
Info
Parameter
Check
1)
Standard:
Output 1 = alarms | Output 2 = M01 min. pressure.
2)
Actuation of an external water make-up device.
3)
:
Terminal plan page 64,
if
þ
selected, switches the Invers
output (NO
→
NC).
4)
Relevant only if «water make-up active».
5)
For messages M27, M28, M30, ..., please contact the
IMI Hydronic Engineering’s customer service. The
equipment may have a fault in the electronics and may not
work correctly.
If message M29 appears when the equipment is first
switched on or during entering of the parameters and sub-
sequent power loss then the unit does not have a fault and
M29 can be cancelled.
However if M29 appears during normal operation it may
mean a fault with the electronics and the unit may not work
correctly. Please contact the IMI Hydronic Engineering’s
customer service.
6)
Set nominal volume VN of primary vessel, or of Statico if
water make-up is pressure-dependent.
If more than one vessel: Set number * VN vessels.
7)
Max. make-up quantity calculated by BrainCube has been
exceeded.
Risk of corrosion in the system.
Leakages in the system should be corrected.
8)
For Pleno PI 6.2. only.
9)
Display:
- Total make up volume,
- Allowable make up volume during set period
(default 12 months). If exceeded alarm M14 triggers,
- Water make-up volume up to date.
Note.The allowable make up volume can be manually
adjusted. If it is set to 0 the BrainCube will calculate the
optimum value.
Caution! Corrosion may occur if set to high values.
10)
Not with key lock on
:
page 56.
11)
Mode «Initial filling» can be activated
:
page 53.
12)
Display for pressure-dependent water make-up only
:
page 66.
13)
Check the date and time and adjust if necessary.
14)
Only relevant if receiving external make-up signals though
RS 485-1 interface. Display of BrainCube No. from which
make-up signals are received.
Factory setting: BrainCube 1 (can be changed by
IMI Hydronic Engineering’s Customer Service to
BrainCube 2, 3 or 4).
MSBX
423
Link-up information***
BrainCube 1, in this case: M = Master*
BrainCube 2, in this case: S = Slave*
BrainCube 3, in this case: B = stand alone**
BrainCube 4, in this case: X = not connected
* Master-slave parallel operation
** Individual operation, for example Vento
*** If the RS 485-1 cabling has been completed correctly
(
:
page 16) and the signal is steady, e.g. MSBX
appears continuously. If the display changes, for exam-
ple from MSBX to SSBX or XXXX, then the interface
signal is not stable and must be checked.
The start-up menu can be perma-
nently hidden to stop unauthorised
tampering. It can be recalled in the
same way:
1. press
menu,
2. press
esc
and hold until 000
appears in the top left of the
display,
3. continue to hold
esc
and use the
scroll
button to enter 423 (4 clicks
right, 2 clicks left , 3 clicks right),
4. release
esc
.
9)
11)
1)
10)
10)
10)
10)
6)
12)
12)
14)