background image

5 of 23

The  diagram  above  shows  the  power  supply 
connections  to  a  single  phase  Source  Controller. 
The Live supply is connected directly to one of the 
channel MCBs or Mains Isolator if fitted. These are 
factory  fitted  with  a  busbar  linking  them  together. 
Do  not  remove  the  busbar  or  any  other  cables 
already  connected  to  the  MCBs  or  Isolator.  The 
maximum supply cable size is 16mm2.

The Neutral supply cable is connected to the neutral 
busbar  terminal  (except  in  the  case  of  a  Source 
Controller  fitted  with  Neutral  disconnect  circuit 
breakers, where connection is to the neutral busbar 
fitted to circuit breakers).

An earth connection must be made to the chassis, 
using the Earth stud. It is important that all supply 
and  neutral  connections  are  tight.  There  is  also 
a  diagram  on  the  cover  of  the  unit  showing  the 
connections.

Supply & Load Cable Terminations

Connections  to  3-Phase  units  are  similar,  except 
that  live  connections  must  be  made  to  three 
sequential  MCB’s.  For  example  RED  to  MCB  1; 
YELLOW  to  MCB  2;  BLUE  to  MCB  3.  The  MCBs 
are  fitted  on  the  supply  side  with  a  3-phase 
busbar  which  distributes  the  incoming  supply 
sequentially to all twelve breakers.

Load Cable Terminations

Load  cables  are  connected  to  the  column  of 
terminal  blocks  located  on  the  left  hand  side  of 
a  Source  Controller.  These  terminals  are  labelled 
L1,E,  N1  L2,E,  etc…  and  will  accept  up  to  6mm2 
cables. 

It  is  important  that  each  load  circuit  neutral  is 
connected  to  the  appropriate  neutral  terminal 
within  the  Source  Controller.  Failure  to  observe 
this could result in electrical interference affecting  
other  equipment.  Do not use a common  neutral
for multiple loads. 

The  Load  terminals  of 3  phase units are phase 
sequential as follows: 
 

L1      Phase 1 (R)

 

L2      Phase 2 (Y)

 

L3      Phase 3 (B) 

 

L4      Phase 1 (R)  

 

L5      Phase 2 (Y)

 

L6      Phase 3 (B)

 

.

 

.

 

.

 

L11    Phase 2 (Y)

 

L12    Phase 3 (B)

Note   

A

daptive  dimmers  (Source  Controllers  with 

prefix  SCA.....)  are  shipped  in  Switch  mode, 
and  will  be  set  (according  to  type  of  connected 
load)  by  the  commissioning  engineer.  Please 
retain all information concerning the type of load 
transformers  that  are  installed  (for  each  dimmer 
channel), so as to assist this process.

WARNING:

  Meggers  must  not  be  used  on  any 

circuitry that is connected to iLight equipment. To 
avoid damage, load cables must be disconnected 
prior to any such testing. 

HF  Ballast  Controllers  -  Connection  of 
low voltage cables 

(Applies  only  to  Source  Controllers  with  prefix 
SCH...) For each individual load circuit, there should 
be a pair of cables linking all ballast LV connections 
together  (paying  due  attention  to  polarity),  and 
terminating  at  the  relevant  connections  in  the 
Source Controller. 

4 Channel inductive version shown

IMPORTANT:

Ensure that load cables are connected to the 

relevant 

type

  of  Source  Controller  in  accordance  with  iLight 

project  drawing  (normally  supplied  with  quotation). 
For example:
Source Controllers with part no. SCI..... are dimmers, 
eg for tungsten or inductive loads.
Source  Controllers  with  part  no.  SCI08.....  are  dual 
units, incorporating four dimmers (O/P’s 1 to 4) and 
four O/P’s (5 to 8) with corresponding 0-10v (or DSI) 
connections for HF Ballasts.
Source  Controllers  with  part  no.  SCH.....  are  HF 
ballast controllers, eg for 0-10v fluorescent fittings.
Source Controllers with part no. SCS..... are switching 
units, eg for non-dimmable luminaires.
Source Controllers with part no. SCA..... are adaptive 
dimmers  -  eg  where  there  is  a  mixture  of  inductive 
and capacitive loads.
Source  Controllers  with  part  no.  SCT.....  are  trailing 
edge dimmers - eg where “trailing edge” dimming is 
required on some circuits.

Supply Cable Terminations

INTELLIGENT  CONTROLS

Содержание SCI0405

Страница 1: ...N Network 8 ASCII control messages 9 Typical system schematics 10 Service switches and LEDs 12 Specifications Inductive H F Ballast Power Switching Adaptive Trailing Edge Instruction Manual Read this document prior to installation Source Controllers INTELLIGENT CONTROLS ...

Страница 2: ......

Страница 3: ...2 of 23 INTELLIGENT CONTROLS ...

Страница 4: ...e Controllers require ventilation and have slots on all sides to allow for a convection flow of air through the unit For this reason it is important to orientate the unit correctly and allow a minimum space between adjacent Source Controllers and other surfaces A minimum of 100mm of free space should be left either side of a Source Controller or between adjacent Controllers IMPORTANT NOTE Mounting...

Страница 5: ...ected by 5Amp MCB s a supply capable of delivering more than 10Amps could be used but it is recommended that it should not exceed the rating shown on the label fitted inside the door Example 2 Fluorescent lamps with dimmable HF ballasts connected to a 4 channel 10A High Frequency Ballast Source Controller SCH0410S Channel 1 load is 8 x 58 Watt tubes Channel 2 load is 16 x18 Watt tubes Channel 3 lo...

Страница 6: ...hase sequential as follows L1 Phase 1 R L2 Phase 2 Y L3 Phase 3 B L4 Phase 1 R L5 Phase 2 Y L6 Phase 3 B L11 Phase 2 Y L12 Phase 3 B Note Adaptive dimmers Source Controllers with prefix SCA are shipped in Switch mode and will be set according to type of connected load by the commissioning engineer Please retain all information concerning the type of load transformers that are installed for each di...

Страница 7: ...ed at 0V and DIM2 If there is any doubt concerning which cable carries mains this must be resolved using a voltmeter before connecting to the Source Controller Connecting a mains potential cable to the Low Voltage terminals will damage the unit and invalidate warranty HF Ballast types The Source Controller is able to control either Analogue or DSI digital ballasts with each channel individually co...

Страница 8: ...es are installed every iCAN network requires two Termination resistors only iCANnet Connections RS485 Control The RS485 Control terminals are located adjacent to the iCAN network terminals The terminals to be used are labelled RS485 RS485 0V See the ASCII control message section on page 13 RJ12 Connector The Source Controller is fitted with an RJ12 socket to allow local connection of a handheld pr...

Страница 9: ... Number valid for 01 to 99 Axx defines the Area Number valid for 01 to 99 1 3 5 Command SC Set Channel Level This message sets the level of a channel in an area The syntax is SCxx Axx Lxx Fxx cr SCxx defines the channel number where xx is valid from 00 to 99 Channel 00 affect ALL channels in an area Axx defines the Area Number valid for 00 to 99 Lxx defines the Level valid for 00 to 99 in and FF f...

Страница 10: ...k cables being terminated If iCANnet cables are terminated after Source Controllers have been energised it should be noted that cables will be carrying low voltage signals and mis connection of these could result in damage to other devices on the network Factory Set Source Controller Settings All channels set to Area 1 Physical Channel No Virtual Channel No Power Up Scene Last Scene Selected From ...

Страница 11: ...work Sending a message to identify the device on the network The LEDs indicate the following l Normal operation l Message transmission and receipt l Override status ICANnet error status will occur when a Source Controller is not connected to an iCAN network for any reason Once either connected to a network of one or more other devices which are powered the error status will be removed It is still ...

Страница 12: ...General Specifications 11 of 23 INTELLIGENT CONTROLS ...

Страница 13: ...l One set of terminals for alarm input Electrical Data Terminal Sizes l Loads maximum cable size 1 x 4 mm2 or 2 x 2 5 mm2 per circuit l iCANnet cable size 5 x 1mm2 l Audio Visual Port RS485 2 x 1mm2 l Alarm input 2 x 1mm2 Memory l FLASH memory to be able to upgrade firmware EEPROM for 128 scene memory Fade Times l 0 1 seconds to 60 minutes Mains Stabilisation l 50 1 Mains Isolators Isolators are s...

Страница 14: ...410 l 4 x 40 Amp rated Triacs SCI1205 SCI1210 SCI1220 l 12 x 40 Amp Triacs Switched Outputs l The Dimmed outputs may be configured as switches for non dimmed loads They require a minimum load of 30mA for them to latch Before connecting Discharge lamps consult with the iLight help desk Terminal Sizes l Incoming supply maximum cable size 10mm2 SCI0405S Single pole SCI0405N Neutral disconnect SCI0410...

Страница 15: ...12 iCANnet Socket Control Board 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Channel Circuit Breakers MAINS IN RS485 Alarm Terminals iCANnet Terminals ...

Страница 16: ...correspond to input supply voltage l Maximum cable size 10mm2 SCH1200T l Incoming supply maximum cable size 2 5mm2 l Ballast output maximum cable size 12 pairs 2 5 mm2 per circuit SCH0410S Single pole 4 channels SCH0410N Neutral disconnect SCH0410D Double pole SCH1210S Single pole 12 Channels SCH1210N Neutral disconnect SCH1210D Double pole SCI0805T Single pole Dual unit SCI0805S Single pole SCI08...

Страница 17: ...Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Mains Supply In Supply Load Cable entry knockouts Supply Load Cable entry knockout...

Страница 18: ...PG16 knockout Switched Relay Controllers 17 of 23 Electrical Data Load Types l This unit is designed to work with most lighting load types Please consult with the iLight help desk for guidance on true load calculations Care should be taken when specifying discharge lighting sources Switched Outputs l This device uses 12 x 230 volt 20A resistive and inductive relays Terminal Sizes l Incoming supply...

Страница 19: ...ocket Control Board Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs Channel Circuit Breakers MAINS IN 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 Alarm Terminals iCANnet Terminals ...

Страница 20: ... and 1 x PG29 knockouts l Control Cable Access 1 x PG16 knockout Electrical Data SCA0410 l Maximum Load 40 Amp single phase 40ºC l Maximum Channel Current 10 Amps l Supply 230 volts 10 50 60 Hz optionally 127 volt 60 Hz l Protection 4 x 10 Amp MCB s type C 6KA rated SCA1210 l Maximum Load 40 Amp three phase 40ºC l Maximum Channel Current 10 Amps l Supply 415 230 volts 10 50 60 Hz optionally 220 12...

Страница 21: ...Adaptive Source Controllers 20 of 23 SCA1210S INTELLIGENT CONTROLS ...

Страница 22: ...tches for non dimmed loads They require a minimum load of 30mA for them to latch Before connecting Discharge lamps consult with the iLight help desk Terminal Sizes l Incoming supply maximum cable size 10mm2 SCT0405S Single pole SCT0405N Neutral disconnect SCT0405D Double pole SCT1205S Single pole SCT1205N Neutral disconnect SCT1205D Double pole Common specifications as detailed on page 12 plus the...

Страница 23: ...y Earth Terminals RJ12 iCANnet Socket Control Board 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Isolator MAINS IN RS485 Alarm Terminals iCANnet Terminals ...

Страница 24: ...arks of Cooper Controls Limited All servicing must be referred to iLight Cooper Controls Limited This equipment is designed for professional lighting control and is unsuitable for any other purpose Cooper Controls Limited reserves the right to make changes to the equipment described in this handbook without prior notice Errors and omissions excepted E OE Part No 7385000 Issue 10 January 2008 INTEL...

Отзывы: