Source  Controllers  (Racks)  should  be  located  in  a 
ventilated dry location where the ambient temperature 
is within the operating range of the controller. When 
choosing the installation location take the following 
into account:

l   

Depending  on  the  size  of  the  loads  connected 

 

  to  an  Inductive  or  Adaptive  Source  Controller  

 

  it  will get warm. Adequate ventilation

       should 

be  provided  to  ensure  the  ambient 

 

  temperature does not rise above 40oC.

l   

Allow  adequate  space  for  future  maintenance 

 

  of  the  unit.  Do  not  install  in  a  location  that 

 

  will later be inaccessible.

l   

Instal only on a vertical surface.

l   

Depending  on  Source  Controller  type  and  

 

  the  loads  connected,  Source  Controllers  can 

 

  create  noise.  This  is  caused  by  electrical  noise 

 

  suppression  components  within  the  unit.  The 

 

  noise  is  a  low  level  buzz  that  varies  with  the 

 

  level of dimming. If noise of this type causes a 

 

  problem, 

locate 

the 

Source 

Controller 

 

  elsewhere.

Source Controllers require ventilation and have slots 
on  all  sides  to  allow  for  a  convection  flow  of  air 
through  the  unit.  For  this  reason  it  is  important  to 
orientate  the  unit  correctly  and  allow  a  minimum 
space  between  adjacent  Source  Controllers  and 
other surfaces. A minimum of 100mm of free space 
should  be left  either side of  a Source Controller or
between adjacent Controllers. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

    IMPORTANT NOTE

    Mounting the Source Controller in the wrong 
    orientation, without proper ventilation or with 
    inadequate airflow could result in overheating.

3 of 23

Installation Instructions

If  a  Source  Controller  is  connecting  to  trunking 
of  depth 50mm or less, then it may be coupled
directly as shown below. 

Leave  100mm  of  free  space  between 
other  equipment,  walls  etc.  either  side 
of the equipment. 

 

If  the  trunking  depth  is  greater  than  50mm, 
installation  of  Source  Controllers  should  be  as  
shown below.

Typical installation for trunking less than 50mm 
depth. Source Controller connected directly to 
trunking.

 

Typical  installation  where  trunking  depth  is 
greater  than  50mm.  Controller  connected  to 
trunking using conduit couplers. 

INTELLIGENT  CONTROLS

Содержание SCI0405

Страница 1: ...N Network 8 ASCII control messages 9 Typical system schematics 10 Service switches and LEDs 12 Specifications Inductive H F Ballast Power Switching Adaptive Trailing Edge Instruction Manual Read this document prior to installation Source Controllers INTELLIGENT CONTROLS ...

Страница 2: ......

Страница 3: ...2 of 23 INTELLIGENT CONTROLS ...

Страница 4: ...e Controllers require ventilation and have slots on all sides to allow for a convection flow of air through the unit For this reason it is important to orientate the unit correctly and allow a minimum space between adjacent Source Controllers and other surfaces A minimum of 100mm of free space should be left either side of a Source Controller or between adjacent Controllers IMPORTANT NOTE Mounting...

Страница 5: ...ected by 5Amp MCB s a supply capable of delivering more than 10Amps could be used but it is recommended that it should not exceed the rating shown on the label fitted inside the door Example 2 Fluorescent lamps with dimmable HF ballasts connected to a 4 channel 10A High Frequency Ballast Source Controller SCH0410S Channel 1 load is 8 x 58 Watt tubes Channel 2 load is 16 x18 Watt tubes Channel 3 lo...

Страница 6: ...hase sequential as follows L1 Phase 1 R L2 Phase 2 Y L3 Phase 3 B L4 Phase 1 R L5 Phase 2 Y L6 Phase 3 B L11 Phase 2 Y L12 Phase 3 B Note Adaptive dimmers Source Controllers with prefix SCA are shipped in Switch mode and will be set according to type of connected load by the commissioning engineer Please retain all information concerning the type of load transformers that are installed for each di...

Страница 7: ...ed at 0V and DIM2 If there is any doubt concerning which cable carries mains this must be resolved using a voltmeter before connecting to the Source Controller Connecting a mains potential cable to the Low Voltage terminals will damage the unit and invalidate warranty HF Ballast types The Source Controller is able to control either Analogue or DSI digital ballasts with each channel individually co...

Страница 8: ...es are installed every iCAN network requires two Termination resistors only iCANnet Connections RS485 Control The RS485 Control terminals are located adjacent to the iCAN network terminals The terminals to be used are labelled RS485 RS485 0V See the ASCII control message section on page 13 RJ12 Connector The Source Controller is fitted with an RJ12 socket to allow local connection of a handheld pr...

Страница 9: ... Number valid for 01 to 99 Axx defines the Area Number valid for 01 to 99 1 3 5 Command SC Set Channel Level This message sets the level of a channel in an area The syntax is SCxx Axx Lxx Fxx cr SCxx defines the channel number where xx is valid from 00 to 99 Channel 00 affect ALL channels in an area Axx defines the Area Number valid for 00 to 99 Lxx defines the Level valid for 00 to 99 in and FF f...

Страница 10: ...k cables being terminated If iCANnet cables are terminated after Source Controllers have been energised it should be noted that cables will be carrying low voltage signals and mis connection of these could result in damage to other devices on the network Factory Set Source Controller Settings All channels set to Area 1 Physical Channel No Virtual Channel No Power Up Scene Last Scene Selected From ...

Страница 11: ...work Sending a message to identify the device on the network The LEDs indicate the following l Normal operation l Message transmission and receipt l Override status ICANnet error status will occur when a Source Controller is not connected to an iCAN network for any reason Once either connected to a network of one or more other devices which are powered the error status will be removed It is still ...

Страница 12: ...General Specifications 11 of 23 INTELLIGENT CONTROLS ...

Страница 13: ...l One set of terminals for alarm input Electrical Data Terminal Sizes l Loads maximum cable size 1 x 4 mm2 or 2 x 2 5 mm2 per circuit l iCANnet cable size 5 x 1mm2 l Audio Visual Port RS485 2 x 1mm2 l Alarm input 2 x 1mm2 Memory l FLASH memory to be able to upgrade firmware EEPROM for 128 scene memory Fade Times l 0 1 seconds to 60 minutes Mains Stabilisation l 50 1 Mains Isolators Isolators are s...

Страница 14: ...410 l 4 x 40 Amp rated Triacs SCI1205 SCI1210 SCI1220 l 12 x 40 Amp Triacs Switched Outputs l The Dimmed outputs may be configured as switches for non dimmed loads They require a minimum load of 30mA for them to latch Before connecting Discharge lamps consult with the iLight help desk Terminal Sizes l Incoming supply maximum cable size 10mm2 SCI0405S Single pole SCI0405N Neutral disconnect SCI0410...

Страница 15: ...12 iCANnet Socket Control Board 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Channel Circuit Breakers MAINS IN RS485 Alarm Terminals iCANnet Terminals ...

Страница 16: ...correspond to input supply voltage l Maximum cable size 10mm2 SCH1200T l Incoming supply maximum cable size 2 5mm2 l Ballast output maximum cable size 12 pairs 2 5 mm2 per circuit SCH0410S Single pole 4 channels SCH0410N Neutral disconnect SCH0410D Double pole SCH1210S Single pole 12 Channels SCH1210N Neutral disconnect SCH1210D Double pole SCI0805T Single pole Dual unit SCI0805S Single pole SCI08...

Страница 17: ...Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Mains Supply In Supply Load Cable entry knockouts Supply Load Cable entry knockout...

Страница 18: ...PG16 knockout Switched Relay Controllers 17 of 23 Electrical Data Load Types l This unit is designed to work with most lighting load types Please consult with the iLight help desk for guidance on true load calculations Care should be taken when specifying discharge lighting sources Switched Outputs l This device uses 12 x 230 volt 20A resistive and inductive relays Terminal Sizes l Incoming supply...

Страница 19: ...ocket Control Board Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs Channel Circuit Breakers MAINS IN 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 Alarm Terminals iCANnet Terminals ...

Страница 20: ... and 1 x PG29 knockouts l Control Cable Access 1 x PG16 knockout Electrical Data SCA0410 l Maximum Load 40 Amp single phase 40ºC l Maximum Channel Current 10 Amps l Supply 230 volts 10 50 60 Hz optionally 127 volt 60 Hz l Protection 4 x 10 Amp MCB s type C 6KA rated SCA1210 l Maximum Load 40 Amp three phase 40ºC l Maximum Channel Current 10 Amps l Supply 415 230 volts 10 50 60 Hz optionally 220 12...

Страница 21: ...Adaptive Source Controllers 20 of 23 SCA1210S INTELLIGENT CONTROLS ...

Страница 22: ...tches for non dimmed loads They require a minimum load of 30mA for them to latch Before connecting Discharge lamps consult with the iLight help desk Terminal Sizes l Incoming supply maximum cable size 10mm2 SCT0405S Single pole SCT0405N Neutral disconnect SCT0405D Double pole SCT1205S Single pole SCT1205N Neutral disconnect SCT1205D Double pole Common specifications as detailed on page 12 plus the...

Страница 23: ...y Earth Terminals RJ12 iCANnet Socket Control Board 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Isolator MAINS IN RS485 Alarm Terminals iCANnet Terminals ...

Страница 24: ...arks of Cooper Controls Limited All servicing must be referred to iLight Cooper Controls Limited This equipment is designed for professional lighting control and is unsuitable for any other purpose Cooper Controls Limited reserves the right to make changes to the equipment described in this handbook without prior notice Errors and omissions excepted E OE Part No 7385000 Issue 10 January 2008 INTEL...

Отзывы: