Example: dST for window function
Condition
Reaction
1 Volumetric flow quantity Q reaches LFC
dST starts, output becomes active
2 dST elapsed, Q reached good range
Output remains active
3 Q above SP (leaves good range)
Output is reset
4 Q again below SP
Output becomes active again
5 Q below rP (leaves good range)
Output is reset again
6 Q reaches again LFC
dST starts, output becomes active
7 dST elapsed, Q has not reached good
range
Output is reset
8 Q reaches good range
Output becomes active
4.8 Low flow cut-off (LFC)
With the function Low Flow cut-off small volumetric flow quantities can be sup-
� Flows below the LFC value are evaluated by the sensor as
standstill (Q = 0)�
4.9 IO-Link
This unit has an IO-Link communication interface which enables direct access to
process and diagnostic data� In addition it is possible to set the parameters of the
unit during operation� Operation of the unit via IO-Link interface requires an IO-
Link capable module (IO-Link master)�
With a PC, suitable IO-Link software and an IO-Link adapter cable communication
is possible when the system is not in operation�