4.6 Measured value damping (dAP)
The damping time allows to set after how many seconds the output signal has
reached 63 % of the final value if the flow value changes suddenly� The set damp-
ing time stabilises the outputs, the display and the process value transfer via the
IO-Link interface� The signals [UL] and [OL]
are defined
under consideration of the damping time�
4.7 Start-up delay (dST)
The start-up delay [dST] influences the switching outputs of the volumetric
flow monitoring�
If the start-up delay is active ([dST] > [0]), note: As soon as the volumetric flow
, the following processes are carried out:
> The start-up delay is activated�
> The outputs switch as programmed: ON for NO function, OFF for NC function�
After the start of the start-up delay there are 3 options:
1� The volumetric flow increases quickly and reaches the set point / good range
within [dST]�
> Outputs remain active�
2� The volumetric flow increases slowly and does not reach the set point /good
range within [dST] > Outputs are reset�
3� Volumetric flow quantity falls below [LFC] within [dST]�
> Outputs are reset at once; [dST] is stopped�