11.3.5 Set switch-off delay [dr1]
►
Select [dr1] and set the value between 0�0 and 60 s�
In accordance with VDMA, the switch-off delay has an effect on [rP1]� The
setting for [ou1] has no significance�
dr1
11.3.6 Define switching logic [P-n]
►
Select [P-n] and set [PnP] or [nPn]�
P-n
11.3.7 Set response of the output in case of a fault [FOU1]
The response of the output OUT-OP (overflow prevention) is fixed: OUT-
OP
opens
in case of a fault!
►
Select [FOU1] and set the value:
FOU1
[On] = Output switches ON in case of a fault�
[OFF] = Output switches OFF in case of a fault�
A fault is for example: defective hardware or signal quality too low� Overflow
is not considered to be a fault
�
11.3.8 Configure display [diS]
►
Select [diS] and set the value:
diS
[On] = The display is switched on in the operating mode�
Update of the measured values every 500 ms
[OFF] = The display is switched off in the operating mode� When one of
the buttons is pressed, the current measured value is displayed
for 30 s� The indicator LEDs remain active even if the display is
deactivated�
11.3.9 Reset all parameters to factory setting [rES]
►
Select [rES]
►
Press and hold [Set] until [----] is displayed�
►
Briefly press [Mode/Enter]�
> The unit reboots and the factory settings are restored�