26
12.3 Error indications
Possible cause
Recommended measures
[Err]
Fault in the electronics
►
Replace the unit�
[SEnS]
• Interfering sources (e�g� EMC)
• Faulty wiring
• Problems with the supply
voltage
►
Check electrical connection�
►
Check connection between the
sensor and the tank ground�
[FAIL]
Wrong password or error during
adjustment of the overflow
prevention OP:
• Overflow prevention covered by
the medium during adjustment�
• Overflow prevention soiled�
• Minimum distances too short
• Mounting element detected
below the overflow prevention
• Measured value not constant
►
Enter a valid password
In case of adjustment errors:
►
Lower the level, if possible�
►
Clean the probe�
►
Observe the notes on installation�
►
Correct the position of the overflow
prevention OP�
►
Repeat the adjustment�
[SC1] +
LED 8
Flashing: Short circuit in
switching output OUT1
►
Remove the short circuit�
[SC�OP] +
LED 7
Flashing: Short circuit in
switching output OUT-OP
►
Remove the short circuit�
[SC] + LED 7
[SC] + LED 8
Flashing: Short circuit in both
switching outputs�
►
Remove the short circuit�
[PARA]
Faulty data set
►
Reset to factory settings [rES]�