![IFM LK122 Series Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/ifm/lk122-series/lk122-series_operating-instructions-manual_620717019.webp)
19
UK
Timeout:
If no button is pressed for 30s during programming, the unit returns to the
operating mode with unchanged values (exception: cOP)�
Locking/unlocking:
The unit can be locked electronically to prevent unauthorised setting
(factory setting: not locked)�
►
Make sure that the unit is in the normal operating mode�
To lock the unit:
►
Press both buttons simultaneously for 10 s�
> [Loc] is displayed�
To unlock the unit:
►
Press both buttons simultaneously for 10 s�
> [uLoc] is displayed�
The unit can be configured before or after installation�
Exception: To adjust the overflow prevention [cOP], the unit
must
be
installed in the tank�
11.2 Basic settings
Setting ranges of all parameters:
Factory settings of all parameters:
11.2.1 Set unit of measurement [uni]
►
Enter [uni] before entering the values for SPx, rPx, OP or OFS�
This avoids unintentional wrong settings�
►
Select [uni]
►
Determine unit of measurement: [cm], [inch]
uni
11.2.2 Set offset [OFS]
The zone between tank bottom and lower edge of the measuring probe can be
entered as offset value
►
Set [OFS] before entering the values for SPx, rPx or OP�
This avoids unintentional wrong settings�
►
Select [OFS]�
►
Set the value for the offset� Note the set unit of measurement [uni]�
OFS