6.2.3 Offset for indicating the real level in the tank
The zone between tank bottom and lower edge of the probe can be entered as
offset value [OFS]� So display and switch points refer to the actual level (point of
reference = tank bottom)�
For [OFS] = [0]: The reference point is the lower edge of the measuring
probe�
The set offset only refers to the display on the unit� It has no effect on the
process value transmitted via IO-Link� The OFS parameter, however, is
correctly transmitted via IO-Link and can therefore be taken into account
6.2.4 Defined state in case of a fault
If a fault is detected or if the signal quality is below a minimum value, the outputs
pass into a defined state� For this case, the response of the output OUT1 can be
�
The response of the output OUT-OP (overflow prevention) is fixed:
it
opens
in case of a fault�
6.2.5 IO-Link function
This unit has an IO-Link communication interface which enables direct access to
process and diagnostic data�
In addition it is possible to set the parameters of the unit while it is in operation�
Operation of the unit via an IO-Link interface requires an IO-Link capable module
(IO-Link master)�
With a PC, suitable IO-Link software and an IO-Link adapter cable communication
is possible when the system is not in operation�
The IODDs necessary for the configuration of the unit, detailed information about
process data structure, diagnostic information, parameter addresses and the
necessary information about the required IO-Link hardware and software can be
found at www�ifm�com�