30
13.3.2 Definition "from the bottom"
Response level (z) of the overflow prevention OP from the tank bottom is defined�
• Without offset ([OFS] = [0]): [OP] = z - u
• With offset ([OFS] = u):
[OP] = z
Example:
z = 18�0 cm (from the tank bottom), u = 1�0 cm
Without offset: [OP] = 18�0 cm - 1�0 cm = 17�0 cm
With offset: [OP] = 18�0 cm
Round the calculated value to the next lower adjustable value
13.4 Setting ranges [SP1] / [FH1] and [rP1] / [FL1]
Table 13-3
LK1222
LK1223
LK1224
[cm]
[inch]
[cm]
[inch]
[cm]
[inch]
[SP1] / [FH1] 2�5���20�0 1�0���7�8
3�5���39�0 1�4���15�4
6���59
2�5���23�5
[rP1] / [FL1]
2�0���19�5 0�8���7�6
3�0���38�5 1�2���15�2
5���58
2�0���23�0
Step
increment
0�5
0�2
0�5
0�2
1
0�5
The indicated values refer to the lower edge of the probe�
The values apply if [OFS] = [0]�
If [OFS] > [0], they increase by the set offset value�