6
4 Function
4.1 Process measured signals
•
The unit displays the current process values�
•
It generates 2 output signals according to the parameter setting�
OUT1: 4 selection options
Parameter setting
-Switching signal for volumetric flow quantity limit
value
-or switching signal for flow velocity
-or pulse signal for quantity meter
-or switching signal for preset counter
OUT2: 6 selection options
Parameter setting
-Switching signal for volumetric flow quantity limit
value
-or switching signal for flow velocity limit value
-or switching signal for temperature limit value
-or analogue signal for volumetric flow quantity
-or analogue signal for flow velocity
-or analogue signal for temperature
If not used as an output, OUT2 (pin 2) can instead be
used as an input for an external reset signal�
4.2 Volumetric flow monitoring
The volumetric flow is monitored by a calorimetric measuring system, the meas-
ured signals are evaluated by the electronics�
•
2 switching signals for volumetric flow limit values can be provided (output 1
and output 2). On the switching functions → 4.5.
•
An analogue signal which is proportional to the volumetric flow (4���20 mA) can
be provided on output 2. On the analogue functions → 4.6.
4.3 Consumed quantity monitoring
The unit has an internal quantity meter which continuously totals the volumetric
flow quantity� The sum corresponds to the current consumed quantity since the
last reset�
•
The current meter reading can be displayed�