9.4 Settings for temperature monitoring
9.4.1 Configure limit value monitoring with OUT2
►
Select [SEL2] and set [TEMP]�
►
Select [OU2] and set the switching function�
-[Hno] = hysteresis function/normally open�
-[Hnc] = hysteresis function/normally closed�
-[Fno] = window function/normally open�
-[Fnc] = window function/normally closed�
►
Select [SP2] and set the value at which the output switches�
►
Select [rP2] and set the value at which the output resets�
9.4.2 Configure analogue value for temperature
►
Select [SEL2] and set [TEMP]�
►
Select [OU2] and set the function�
-[I] = temperature-proportional current signal (4…20 mA)�
►
Select [ASP] and set the value at which the minimum value is provided�
►
Select [AEP] and set the value at which the maximum value is provided�
9.5 User settings (optional)
9.5.1 Set standard unit of measurement for volumetric flow
►
Select [Uni] and set the unit of measurement
-[nm3m] = volumetric flow quantity in standard cubic metres/minute
-[nm3h] = volumetric flow quantity in standard cubic metres/hour
-[nmS] = flow velocity in standard metres / second
The setting only has an effect on the volumetric flow value� The meter read-
ing (consumed quantity) is automatically displayed in the unit of measure-
ment providing the highest accuracy�