25
UK
9.7 Set preset counter / pulse value (ImPS)
The unit has 4 setting ranges:
LED
Display
Value
Step
increment
1
4
0 0 0 1
���
9 9 9 9
1���9999 Nm³
1 Nm³
2
4 + 6
1 0 �0 0
���
9 9 �9 9
10 000���99 990 Nm³
10 Nm³
3
4 + 6
1 0 0 �0 ���
9 9 9 �9
100 000���999 900 Nm³
100 Nm³
4
4 + 6
1 0 0 0
���
1 0 0 0
1 000 000 Nm³
Setting operation
:
► Set [OU1] to [ImP] (→ 9.3.2).
►
Press [Mode/Enter] until [ImPS] is displayed�
►
Press and hold [Set]�
> The current numerical value flashes for 5 s, then the first of the 4 digits be-
comes active (digit flashes, can be changed)�
►
Set the requested value as shown in the following table�
►
First select the requested setting range (1, 2, 3 ���)�
►
Then enter the number from left (first digit) to right (fourth digit)�
►
Press [Mode/Enter] briefly when all 4 digits are set�
As soon as the first digit flashes there are 3 options:
►
Briefly press [SET]
1 x�
The flashing digit increments� 9 is followed by 0 - 1 - 2, etc�
8 1� 2 3
[SET] pressed 1 x 9 1� 2 3
[SET] pressed 1 x 0 1� 2 3
[SET] pressed 1 x 1 1� 2 3