![IFM efector100 G1503S Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/ifm/efector100-g1503s/efector100-g1503s_operating-instructions-manual_620813029.webp)
29
UK
8.3.3 Fault diagnosis
In case of a fault switch the safety relay off and on again�
LED display
Cause of the fault
Troubleshooting
• No voltage supply
• Overvoltage
• Connection A1/A3 or A1/A2
reversed
►
Check wiring
►
Check power supply
• Wire break
• Feedback contacts open
• Time-dependent contacts
►
Check wiring
►
Switch the safety relay off
and on again
• When voltage is applied:
feedback contacts open
►
Check output circuit
►
Check feedback contacts
►
Exchange external contactor
• Wiring fault
• Missing link Y4/Y5
• Short circuit
• Inputs S34 and S43 activated
when voltage is applied
►
Check wiring
►
Deactivate inputs and
RESET or voltage failure
• Connections A3/A2
exchanged
►
Check wiring
• Missing link Y4/Y5
►
Check wiring
• Overvoltage
• Undervoltage
►
Check wiring
►
Check power supply
Содержание efector100 G1503S
Страница 1: ...Original operating instructions Safety relay with semiconductor outputs G1503S UK 80236593 00 02 2016 ...
Страница 9: ...9 UK 5 2 Block diagram L L ...
Страница 16: ...16 Input circuit Output status LED display L L ...
Страница 17: ...17 UK Input circuit Output status LED display L L ...
Страница 33: ...33 UK 8 4 2 Function Input circuit Output status LED display L L N O contact activated ...
Страница 34: ...34 Input circuit Output status LED display L L N O contact activated ...
Страница 35: ...35 UK Input circuit Output status LED display L N O contact activated ...
Страница 40: ...40 Input circuit Output status LED display L L N O contact activated ...
Страница 47: ...47 UK ...