10
6 Installation
►
Mount the unit on a DIN rail in a housing protected against dust and humidity
(min� IP54 - degree of soiling 2)�
7 Electrical connection
►
Use 60/75°C copper conductors only�
7.1 Supply voltage
The external supply unit must have a safe separation� In case of a fault the
voltage can exceed the value of 60 V DC for a maximum of 200 ms, but
must not exceed the value of 120 V DC�
►
Connect supply voltage
L+
Manual reset
L+
RESET
For safety reasons the unit can only be restarted by
separation from the supply voltage in case of a fault�
It is thus recommended to install a RESET switch in
series with the L+ circuit�
After power on or a RESET the unit carries out self diagnostic functions� After this
self diagnosis the unit is ready for operation�
Содержание efector100 G1503S
Страница 1: ...Original operating instructions Safety relay with semiconductor outputs G1503S UK 80236593 00 02 2016 ...
Страница 9: ...9 UK 5 2 Block diagram L L ...
Страница 16: ...16 Input circuit Output status LED display L L ...
Страница 17: ...17 UK Input circuit Output status LED display L L ...
Страница 33: ...33 UK 8 4 2 Function Input circuit Output status LED display L L N O contact activated ...
Страница 34: ...34 Input circuit Output status LED display L L N O contact activated ...
Страница 35: ...35 UK Input circuit Output status LED display L N O contact activated ...
Страница 40: ...40 Input circuit Output status LED display L L N O contact activated ...
Страница 47: ...47 UK ...