18
8.1.3 Fault diagnosis
In case of a fault switch the safety relay off and on again�
LED display
Cause of the fault
Troubleshooting
• No voltage supply
• Overvoltage
• Connection A1/A3 or A1/A2
reversed
►
Check wiring
►
Check power supply
• Wire break
• Feedback contacts open
►
Check wiring
►
Switch the safety relay off
and on again
• When voltage is applied:
feedback contacts open
►
Check output circuit
►
Check feedback contacts
►
Exchange external
contactor
• Wiring fault
• Short circuit
• Inputs S34 and S43 “1” when
voltage is applied
►
Check wiring
►
Switch the fail-safe sensor/
switch off and on again
• Short circuit S33/S43
►
Check wiring
• Short circuit S33/S43
►
Check wiring