P06
edge evaluation
0 = one-fold evaluation
1 = two-fold evaluation
2 = four-fold evaluation
0
P07
change of signs
0 = active; 1 = not active
0
P08
multiplication factor
multiplication of the input pulses by factor
0.0001 ... 9.9999
(if P11 is set to 4 or 5, only factors
≤
1.0000 should be
used)
1,0000
P14
display brightness
0 ... 9 = level of brightness
5
P16
basic setting
1 = all parameter values are set to the basic setting
0
P18
input block for preset
0 = preset can be changed
1 = preset cannot be changed (blocked)
0
P19
limitation of the counting frequency in the VRD mode
0 = max. counting frequency = 10 Hz
(max. count value: ± 32768)
1 = max. counting frequency = 20 kHz
1 1
(IN-A = 1
IN-B = 1)
P21
relay switches if value of the preset value is positive or
negative
0 = active; 1 = not active
1
P99
display of the current software version and the version number
P15
external reset / preset
0 = preset if pulse on terminal 13
1 = reset if pulse on terminal 13
1
P12
fleeting time relay
0.1s ... 9.9s adjustable in steps of 0.1s
1,0
P10
relay function
0 = fleeting; 1 = solid state until reset / preset
0
P11
output performance of the relay
0 = relay switches at 0
1 = relay switches at preset
2 = relay switches at
≥
preset, de-energises at < preset
3 = relay switches at
≤
preset, de-energises at > preset
4 = relay switches at 0 and sets autopreset
(sets the counter to preset)
5 = relay switches at preset and sets autoreset
(sets the counter to 0)
1