DP2122
Speed monitor
22
8.4.6 dS ─ switching delay
Delay when the output changes to the active switching status.
Setting range: 0...99.99 s
Resolution 0.01 s
8.4.7 dr ─ switch-off delay
Delay when the output changes to the idle state.
Setting range: 0...99.99 s
Resolution 0.01 s
8.4.8 P-n ─ output configuration
•
[PnP] = load connected to ground
•
[nPn] = load connected to VBB
8.5 Parameters for OUT2 (SSC2)
With the exception of P-n: see Parameters for OUT1 (SSC1) (
8.6 Parameters of the extended functions (EF)
8.6.1 rES ─ restore factory setting
Resets all parameters to the Factory settings (
u
Select [rES].
u
Press [●].
u
Press and hold [▲] or [▼] until [----] is displayed.
u
Briefly press [●].
8.6.2 Lo/Hi ─ min/max measured input values
[Lo] = lowest measured value
[Hi] = highest measured value
Delete memory:
u
Select [Hi] or [Lo].
u
Press and hold [▲] or [▼] until [----] is displayed.
u
Briefly press [●].
8.6.3 dSt ─ start-up delay time
Setting of the delay time between switch-on/reset of the unit and start of speed evaluation.
8.6.4 ScAL ─ set decimal point
Operating mode 1: Operating modes (