IO-Link master with USB interface 1 port IP 65 / IP 67
18
>
9.3.1
Note: Device validation and data storage
60832
The user can choose how the IO-Link ports are to behave with regards to the device validation and the
storage / recovery of parameter data of the connected IO-Link device.
The following options are available:
Option
Validation of the IO-Link
device
Storage of the parameter values Recovery of the parameter
values
[No check and clear] no
no
no
[Type compatible
V1.0 device]
yes, test the compatibility with
IO-Link standard V1.0
no
no
[Type compatible
V1.1 device]
yes, test the compatibility with
IO-Link standard V1.1
no
no
[Type compatible
V1.1 device with
Restore]
yes, test the compatibility with
IO-Link standard V1.1 and
identity of design (vendor ID
and device ID)
yes, automatic storage of the
parameter values; changes of the
current parameter values will be
stored
yes, recovery of the parameter
values when connecting an
identical IO-Link device with
factory settings
[Type compatible
V1.1 device with
Restore]
yes, test the compatibility with
IO-Link standard V1.1 and
identity of design (vendor ID
and device ID)
no, there is no automatic storage
changes of the current parameter
values will not be stored
yes, recovery of the parameter
values when connecting an
identical IO-Link device with
factory settings