IO-Link Master with AS-Interface Interface StandardLine 2 Ports IP 65 / IP 66 / IP 67
79
>
Command response
59358
Byte
Bit
7
6
5
4
3
2
1
0
0
0x00
1
Block Counter
2
Command status (
→
list "Diagnostic codes")
3
0x05
4
IO-Link Port
5
Mode
6
Type
7
Event Code (MSB)
8
Event Code (LSB)
9...160
ignored
Legend:
[IO-Link Port] IO-Link Port
8 bits
0x01
IO-Link Port 1
0x02
IO-Link Port 2
[Mode]
Occurrence of the error that has triggered the
event
8 bits
0x40
Individual message or warning
0x80
Error or warning has appeared
0xC0
Error or warning has disappeared
[Type]
Type of error that has triggered the event
8 bits
0x10
Message
0x20
Warning
0x30
Error
[Event Code] Error cause
Event Code = 0x1234
Event Code (MSB) = 0x12
Event Code (LSB) = 0x34
16 bits
per byte: 0x00...0xFF
depends on the IO-Link device (
→
IODD of
the IO-Link devices)
Diagnostic codes:
0x01
OK
0x04
Blocked Port - another acyclic access is still active
0x05
Command Error, no response data available
0x07
Wrong Target ID (wrong Port number)
0x08
Invalid length (wrong input parameter length)
0x0A
Wrong Block ID