IO-Link Master with AS-Interface Interface StandardLine 2 Ports IP 65 / IP 66 / IP 67
15
>
6.3
Connecting the unit
59326
The AS-i voltage supplies the IO-Link master and the IO-Link supply voltage of the ports. The
AUX voltage is exclusively intended to supply additional AS-devices (daisy chain).
►
Connect the AS-i voltage input to AS-i power supplies only!
►
In case of cables that are longer than 25 m, take the voltage drop and the necessary
minimum supply voltage of 20 V into consideration!
►
Disconnect power.
►
Connect the device to the AS-i supply voltage via the M12 socket
X21 (26...31.6 V DC).
Tightening torque: 0.6...0.8 Nm.
Recommended maximum cable length: 25 m
►
To connect the device, use M12 connectors with at least
protection rating IP 65 / IP 66 / IP 67 (
→
Accessories
(
→
Optional: Supply of an additional AS-i device (daisy chain)
►
Connect the device to the AUX supply voltage via the M12 socket
X21 (24 V DC (20...300 V SELV/PELV)).
►
Connect an additional AS-i device to the M12 socket X22 of the
AC6002 (loop-through function).
Tightening torque: 0.6...0.8 Nm
Recommended maximum cable length: 25 m
►
To connect the device, use M12 connectors with at least
protection rating IP 65 / IP 66 / IP 67 (
→
Accessories
(
→