4.2 Sources of interference in the pipe system
Components integrated in the pipes, bends, valves, reductions, etc lead to turbu-
lence of the medium This affects the function of the unit
Recommendation: Adhere to the distances between sensor and sources of
interference:
D = pipe diameter; S = sources of interference
4.3. Mounting operation
►
Ensure that the system is free of pressure during installation
►
Ensure that no media can leak at the mounting location during installa-
tion
►
Grease the threads of the process connection (1), adapter (2) and nut (3)
Note: The sensor tip (A) must not be in contact with grease
►
Screw the suitable adapter into the process connection
►
Place the flow monitor onto the adapter and tighten the nut Tightening torque
25 Nm Ensure that the unit is correctly oriented