9
UK
7.2 High flow adjustment (optional)
The unit determines the existing flow as normal flow and adapts the display repre-
sentation (all LEDs except the switch point LED light green)
►
Let the normal flow circulate in the installation
►
Press the pushbutton and keep it pressed
> LED 9 lights, after approx 5 s it flashes
►
Release the pushbutton
The unit is now adapted to your flow conditions It passes into the operating mode,
the display should now show example 1
Note: The adjustment affects the switch point: It is increased proportionally (maxi-
mum up to LED 7)
7.3 Set the switch point SP2 (temperature)
►
Briefly press the pushbutton
> The current temperature and the current setting of the switch point are indi-
cated for 5 seconds in steps of 10°C (→ 10.1).
Row of LEDs red = current temperature,
LED green or orange = current switch
point
LED green if OUT = OFF; LED orange if OUT = ON
►
Briefly press the pushbutton within 5 s another time
> The current setting of the switch point is displayed in steps of 1°C and can be
changed
LED green = 1st digit (10 times X °C)
LED green, flashing = 2nd digit (X °C)
here: 51°C
LED green if OUT = OFF; LED orange if OUT = ON
In addition the current temperature is indicated in steps of 10°C by red LEDs
►
Press the pushbutton or
as often as required Each press of the
pushbutton shifts the flashing LED (1st digit) by one position in the indicated
direction