UK
> After 10 s the current setting is displayed: LEDs 59 light orange (= outputs
normally open)
> After approx 15 s LEDs 04 flash orange
►
Release the pushbutton The outputs are changed to normally closed operation
For a new changeover repeat the operation
8.3 Restore the factory setting (reset)
►
Press the pushbutton for at least 15 s
> LED 9 lights, after approx 5 s it flashes
> After approx 15 s LEDs 09 flash orange
►
Release the pushbutton All settings are reset to the factory setting:
-operating area: 5 100 cm/s for water
-switch point S1 (flow): LED 7
-switch point S2 (temperature): LED 0 (4°C)
-output function: NO
-unlocked
8.4 Lock / unlock the unit
The unit can be locked electronically to prevent unintentional settings
►
Press both setting pushbuttons simultaneously for at least 10 s in the operating
mode
> The indication goes out, the unit locks or unlocks
On delivery: unlocked