31
ifm
Operating Instructions IO-Link Master with EtherNet/IP interface StandardLine 8 Ports IP 65 / IP 67 (AL1122)
2017-05-31
Configuration
>
8.1.3
Offline parameter setting
SYS_OBJECTID>
The AL1122 supports the offline parameter setting. In this context, the user creates and stores a
configuration for the unit and the connected IO-Link devices without being connected to the AL1122.
The configuration created in this way can be stored as a file (*.lrp) and loaded to the device and
activated at a later date.
Further information about offline parameter setting:
→ Operating instructions of the parameter
setting software LR DEVICE
>
8.1.4
VPN connection
22762
An active VPN connection blocks the access of the parameter setting software LR DEVICE to
the EtherNet/IP interface of the AL1122.
► Deactivate the VPN connection in order to be able to access the AL1122 with the LR
DEVICE.