Configuration
8.4.1
Registration of the EDS file
1979
ifm provides an EDS file to integrate the AL1122 in a EtherNet/IP projection software. The user can
download the EDS file from the ifm website (
→ the EDS file, all parameters, process data, and their
valid value ranges are defined.
To add the AL1122 to the device catalogue of RSLogix5000:
►
Download the EDS file of the AL1122 from the ifm website.
►
Start RSLogix5000.
►
Select [Tools] > [EDS Hardware Installation Tool].
>
EDS Wizard appears.
►
Register the downloaded EDS file of the AL1122 with the EDS Wizard.
>
EDS Wizard installs the EDS file and adds the AL1122 to the device catalogue.
>
8.4.2
Integrate the AL1122 into the EtherNet/IP network
8015
The device is integrated as module of an I/O scanner in the EtherNet/IP network.
Requirements:
>
The EDS file of the AL1122 is installed (→
Registration of the EDS file
1 Create/open EtherNet/IP project
►
Start RSLogix 5000.
►
Create new EtherNet/IP project.
OR
Open an existing EtherNet/IP project.
2 Configure EtherNet/IP PLC and IO scanner
►
Select and configure EtherNet/IP controller and IO scanner.
>
EtherNet/IP project includes a EtherNet/IP controller and an IO scanner.
3 Integrate AL1122 in project
►
In the Controller Organizer: Right mouse click on the IO scanner.
>
Context menu appears.
►
In the context menu: Select [New Module...].
>
The window [Select Module Type] appears.
►
Select AL1122 and click on [Create].
>
The [New Module] window appears.
►
Enter name and IP address of the AL1122.
►
Click on [OK] to adopt the entered values.
>
RSLogix 5000 adds AL1122 as sub-element of the IO scanner to the project.
4 Save the project
►
Save EtherNet/IP project