C O N F I G U R A T I O N & O P E R A T I O N
Humidifier setting screen
Humidifier se ng screen allows user (mechanical contractor) to set humidifier parameters. Access
to this screen can be restricted with passcode. In this case passcode is 7030
Humidifier Se ng menu is subdivided in 5 screens:
•
Humidifier se ng 1
•
Humidifier se ng 2
•
BMS se ng
•
Main se ng
•
System informa on
Humidifier se ng / se ng 1
Figure 50, Humidifier se ng/se ng 1 screen
41
Drain frequency is to reduce mineral concentration in boiling water
See our guideline below, if
tap (city) water is used
Inactivity drain is to flush cylinder when no demand
If On, set the time with no
demand before flushing
cylinder
You can disable this function
Drain cooling is to reduce temperature of wasted water when draining
Service freq. Is the operation time period before to call for cleaning.
If service Auto off is ON the
humidifier will shut down
when service is due
Drain frequency guideline when tap (city) water is used
In order to avoid foaming, water contained in cylinder needs to be deconcentrated
from time to time from its minerals dissolved content (TDS).
- Traditional way is to drain most of water from cylinder at a fixed freq. Time.
- If cursor is set on ‘’Autodilution’’ (full left) EcoEnerSmart (patented) function is
activated : humidifier will flush a small amount of water and bring equivalent of
new water more frequently; saving energy & water. Autodilution frequency will
auto-adapt in case foam will be detected.
You can disable this function
(if RO or pure water is used)
Reset alarm allows to reset latched alarms