C O N F I G U R A T I O N & O P E R A T I O N
Control se ng / Hi Limit config
Figure 48, Control se ng/Hi Limit config screen
39
Select RH% Hi Limit source from :
On/Off demand
External analog demand
Both
If internal, set the
Setpoint with cursor
Or, if external, set the RH%
Hi limit signal range from
0-10vdc,
2-10Vdc,
4-20mA
If applicable, set the PID
Recommended (default) setting is :
P gain :
60
I gain :
25
D gain :
20
P Band :
0
Dead band :
0