8
Wiring Instructions
Sensor to Converter Connection
There are several options for the Sensor to Converter
interface.
•
HML210 Converter mounted integrally on the sensor
(compact).
•
HML210 Converter mounted remotely from the
sensor (remote). This requires cable assemblies
C015 and C016.
•
HML210 Converter mounted remotely from the
sensor in a panel (remote).
If the HML210 is mounted remotely from the sensor, the
following guidelines must be adhered to:
•
Maximum distance from the HML210 to the sensor
is 30 ft for fluids with a conductivity less than 200µS
(micro siemens).
•
Maximum distance from the HML210 to the sensor
is 65 ft for fluids with a conductivity greater than
200µS.
For applications where these conditions are not met, a
preamplifier is required. This mounts directly on top of
the sensor. With a preamplifier installed, the maximum
distance from the sensor to the HML210 is 1,640 ft
(500m).
NOTE
: For proper installation, the cables must be ordered
with the unit. User supplied cables may void warranty
coverage and could affect the functioning of the meter.
Preamplifier Version
NOTE:
Maximum length of cable C014 is 1,640 ft (500m).
!
!
!
!
!
IMPOR
IMPOR
IMPOR
IMPOR
IMPORT
T
T
T
TANT
ANT
ANT
ANT
ANT
For North American Installations, the installation must be fully in accordance with the National Electrical Code (US)
or the Canadian Electrical Code respectively to maintain the hazardous location ratings on the product.
For European installations, the installation must be fully in accordance with EN60079-14 to maintain the hazardous
location ratings on the product. This may involve using special cable glands for all connections.