28
OFF
Disabled.
# 1 IMP+
Pulse on Channel 1 for positive flowrate.
# 1 IMP-
Pulse on Channel 1 for negative flowrate.
# 1 IMP±
Pulse on Channel 1 for positive and negative flowrate.
# 2 IMP+
Pulse on Channel 2 for positive flowrate.
# 2 IMP-
Pulse on Channel 2 for negative flowrate.
# 2 IMP±
Pulse on Channel 2 for positive and negative flowrate.
# 1 FREQ+
Frequency channel 1 for positive flowrate.
# 1 FREQ-
Frequency channel 1 for negative flowrate.
# 1 FREQ±
Frequency channel 1 for positive and negative flowrate.
# 2 FREQ+
Frequency channel 2 for positive flowrate.
# 2 FREQ-
Frequency channel 2 for negative flowrate.
# 2 FREQ±
Frequency channel 2 for positive and negative flowrate.
SIGN
Flow direction output (Energized = -).
RANGE
Range indication output (Energized = Scale 2).
MAX AL+
MAX direct flowrate output (Energized = Alarm OFF).
MAX AL-
MAX reverse flowrate output (Energized = Alarm OFF).
MAX AL±
MAX direct/reverse flowrate output (Energized = Alarm OFF).
MIN AL+
MIN direct flowrate output (Energized = Alarm OFF).
MIN AL-
MIN reverse flowrate output (Energized = Alarm OFF).
MIN AL±
MIN direct/reverse flowrate output (Energized = Alarm OFF).
MAX+MIN±
MAX and MIN flowrate alarm output (Energized = Alarm OFF).
P. EMPTY
Empty pipe alarm output (Energized = Full pipe).
OVERFLOW
Out of range alarm output (Energized = Flow rate OK).
HARDW AL.
Cumulative alarm output: interrupt coils, empty pipe, measure error (Energized = NO ALARMS
AL.
BATCH AL :BATCH ALARM).
EXT. COMM
.
Only available with data-logger module.
BATCH AL.
Batch alarm output.
BATCH SYN
At the end of a batch, the status output changes.
END BATCH
End batch output (Energized = Batch in progress).
PREBATCH
Pre-batch output (Energized = Prebatch in progress).
6-OUTPUTS
Programming Functions
Out1=
Is the function corresponding to digital output 1.
The functions available for output 1 are listed in the table
on the next page. Press the
key to access
Out1
options. Use the
and
keys to scroll though the
options. Press the
key to accept the option.
Out2=
Is the function corresponding to digital output 2.
The functions are listed in the table below.
Out3=
Is the function corresponding to digital output 3.
The functions are listed in the table on the next page.
This output only appears when an optional module is
installed.
Out4=
Is the function corresponding to digital output 4.
The functions are listed in the table on the next page.
This output only appears when an optional module is
installed.
NOTE: Out4
is the only output which can reach a
frequency of 12.5 kHz.
#1 IMP+
SIGN
50
±
6-OUTPUTS
Out1=
Out2=
Duty cycle1=%
Out mA1=4-20