Operating Instructions

 

IDEM Safety Switches

 

 NET-BOX-CS

 

 

102638 2305 NET-BOX-CS Operating Instructions 

 

4

 

5

 

Protocol Setup 

 

IMPORTANT 

 

The minimum time between the change of a single safe digital input and the 
transmission to the CIP Safety is 32ms. In the case of an input level change at both 
safe inputs at the same time the maximum safe application reaction time is 42ms for 
Interlock/Lock and Estop.  

 

Clear any pre-existing configuration from any safety device before installing it onto a 
safety network. 

 

Commission all safety devices with IP address prior to installing it onto a safety 
network. 

 

When a SIL3 device is configured directly from a workstation, the user should 
compare the transferred SCID and configuration data with the SCID and 
configuration data originally viewed in the workstation. 

 

The configuration software shall assume an ASYNC parameter value of 1. 

 

Configuring an originator with connection data and/or target configuration data 
must be downloaded to the target so it can be tested and verified. Only then can 
SCIDs from the target be confirmed. 

 

Status-Bits reported by the device via CIP Safety messages shall not be used to 
trigger the safety function of a device or system. 

 

The safety-related parts of the EDS (Electronic Data Sheet) of the NET-BOX-CIP 
device shall not be altered. 

 

Each safety device shall have a single physical address that is unique on the devices 
segment. 

 

The maximum operation time (proof-test interval) of the NET-BOX shall not exceed 
20 years. When reaching the proof test interval, the NET-BOX shall be replaced and 
put permanently out of order. 

 

After the detection of a safety critical error, the NET-BOX shall not be kept in fail-
safe state for more than 1 hour. 

 

INFORMATION 

 

The device EDS file can be found via the NET-BOX product page of the IDEM website 
www.idemsafety.com/products or alternatively please contact 

[email protected]

 

 

 

 

Содержание NET-BOX-CS

Страница 1: ...nstructions To request this document in other languages please contact info idemsafety com IDEM Safety Switches NET BOX CS Safety IO Standard IO and Integrated EtherNet IP with CIP Safety Operating In...

Страница 2: ...col Setup 4 Network Address Setup Initial Setting 5 Setting via DIP Switch 5 Setting via DHCP 6 Studio 5000 Ethernet IP Configuration 7 Factory reset 9 Functional Tests 9 6 Data Map 9 7 Diagnostic Ind...

Страница 3: ...idiaries and affiliates are not in a position to guarantee all of the characteristics of a given system or product not design by IDEM All relevant safety regulations and standards are to be observed T...

Страница 4: ...ISATEUR Observe the county specific regulations when installing the device Repair or modification of the NET BOX is not allowed unless authorised by IDEM and carried out according to operating guideli...

Страница 5: ...irements for UL a class 2 power supply must be used INFORMATION When multiple devices are used in a daisy chain arrangement the power bus may be forwarded via the NET BOX device See technical specific...

Страница 6: ...ASYNC parameter value of 1 Configuring an originator with connection data and or target configuration data must be downloaded to the target so it can be tested and verified Only then can SCIDs from t...

Страница 7: ...the final step if the device is powered Remove the lid screws and turn over the NET BOX Lid to locate the DIP switches see below Using a small tool push the required switches to the ON position to set...

Страница 8: ...entify the NET BOX select the NET BOX in the Discovery History window and click Add Relation 4 Configure the required IP address setting in the pop up window and click OK 5 Open an internet browser an...

Страница 9: ...Configuration 1 Download the EDS file for the NET BOX and import to application control software 2 Open or create a project with the PLC CPU Partner and Ethernet IP modules added 3 Right click the Et...

Страница 10: ...customisable NET BOX CS used as example only and set the previously configured IP address 6 Change the Safety Network Number SNN to match that of the controller PLC 7 On the Safety tab uncheck the Con...

Страница 11: ...ce has been installed and setup within the EtherNet IP CIP Safety application control software the following checks are necessary to ensure correct operation of the system Secure mounting of NET BOX w...

Страница 12: ...on to PLC Idle state Red Major Fault Red Flashing Recoverable fault check PLC NET BOX configuration NS Off No IP address set Green Online connection s established Green flash 1Hz Online no connections...

Страница 13: ...ge 24V DC Input Rated Current 2 mA Standard Outputs Output Rated Voltage 24V DC sourced from power connectors Output Maximum Current 500 mA single 1 5 A group OUT1 4 OUT5 8 Test Outputs Parameter Unit...

Страница 14: ...altitude 2000 m Shock and Vibration Tested in accordance with IEC 60068 2 6 and IEC 60068 2 27 Pollution Degree Degree 2 EN 60664 Storage and Operation Reliability Safety Data EN ISO 13849 1 Category...

Страница 15: ...Operating Instructions IDEM Safety Switches NET BOX CS 102638 2305 NET BOX CS Operating Instructions 13 NOTES...

Страница 16: ...BOX THE LISTED DEVICES CONFORM TO THE ESSENTIAL HEALTH AND SAFETY REQUIREMENTS OF THE FOLLOWING EUROPEAN DIRECTIVES AND STANDARDS DIRECTIVES Machinery Directive 2006 42 EC EMC Directive 2014 30 EU ST...

Отзывы: