8
Technical
Device Characteristics
Response time (Safety Inputs)
36 ms max. (Change of input state -> transmission to field bus)
Response time (Safety Outputs)
7.7 ms max. (field bus telegram recvd -> change of output state)
Electrical Data
Operating voltage
24 V DC +10%/-15% (SELV/PELV)
Power Supply UL Requirements
Class 2 power supply must be used.
Current consumption, max.
250 mA (excluding Standard Outputs and Safety Outputs).
Allowed through current (daisy-chain)
5 A
Standard Inputs
Input Rated Voltage
24V DC
Input Rated Current
2 mA
Standard Outputs
Output Rated Voltage
24V DC (sourced from power connectors)
Output Maximum Current
500 mA single / 1.5 A group (OUT1..4 / OUT5..8)
Test Outputs
Parameter
Unit
Min
Typ.
Max
Voltage Test Output High
V
19.2
24
30
Voltage Test Output Low
V
--
High Z
--
Current Test Output High
mA
--
100
100
Current Test Output Low
mA
--
--
0.5
Short Circuit Peak
A
9
17
28
Safety Inputs
Parameter
Unit
Min
Typ.
Max
Voltage Digital Input High
V
15
24
30
Voltage Digital Input Low
V
-3
0
5
Current Digital Input High
mA
2
5
15
Current Digital Input Low
mA
0
--
15
Safety Outputs
Parameter
Unit
Min
Typ.
Max
Voltage Digital Output High
V
19.2
24
30
Current Digital Output High
mA
--
--
500
Current Digital Output Low
mA
--
--
0.5
Inductive Load
H
--
--
0.5
Capacitive Load
uF
--
--
1
Short Circuit Peak
A
2
5