2.2 Wiring IDEC SmartRelay
Use a screwdriver with a 3 mm head to wire IDEC
SmartRelay.
You don’t need wire end ferrules for the connectors. You
can use wires up to the following sizes:
•
1 x 2.5 mm
2
•
2 x 1.5 mm
2
for each second connector compartment
Connecting torque: 0.4...0.5 Nm or 3...4 LBin
Note
Install IDEC SmartRelay in a distribution box or control
cabinet, ensuring that the connectors are covered. If they are
not, there is a danger of touching live parts.
2.2.1
Connecting the Power Supply
FL1A-H10RCB and FL1A-B10RCB are suitable for line
voltages with a rating of 100V AC and 240V AC. Other
Types are suitable for 12V DC, 24V DC or 24V AC supply
voltage. Note the information on connection in the product
information document shipped with your device and the
technical specifications in Appendix A relating to the
permissible voltage tolerances, line frequencies and
current inputs.
Note
Power failure might result in a voltage spike after power
restoration, which may affect certain edge-triggered function
blocks.
Содержание SmartRelay FL1A-H12RCE
Страница 1: ...IDEC SmartRelay Manual March 2001 www idec com ...
Страница 16: ...Getting to Know IDEC SmartRelay 1 6 IDEC SmartRelay User s Manual ...
Страница 32: ...Installing and Wiring IDEC SmartRelay 2 16 IDEC SmartRelay User s Manual ...
Страница 132: ...IDEC SmartRelay Functions 4 64 IDEC SmartRelay User s Manual ...
Страница 184: ...Applications 8 32 IDEC SmartRelay User s Manual ...
Страница 204: ...IDEC SmartRelay Menu Structure E 2 IDEC SmartRelay User s Manual ...
Страница 206: ...Type Numbers F 2 IDEC SmartRelay User s Manual ...
Страница 208: ...Abbreviations G 2 IDEC SmartRelay User s Manual ...