IDEC SmartRelay Functions
4-47
IDEC SmartRelay User’s Manual
Parameters T
H
and T
L
Note the default values for the parameters T
H
and T
L
in
Section 4.3.2.
Timing diagram
Description of function
If the state at the input En changes from 0 to 1, a random
time (on delay time) between 0 s and T
H
is defined and
started. If the state at the input En remains at 1 at least for
the duration of the on delay time, the output is set to 1 after
the on delay time has elapsed.
If the state at the input En switches back to 0 before the on
delay time has elapsed, the timer is reset.
If the state at the input En changes again to 0, a random
time (off delay time) between 0 s and T
L
is defined and
started.
If the state at the input En remains at 0 at least for the
duration of the off delay time, the output is set to 0 after the
off delay time has elapsed.
If the state at the input En switches back to 1 before the off
delay time has elapsed, the timer is reset.
In the event of a power failure, the elapsed time is reset.
En
T starts
Q
T
L
T
H
The bold part of the
timing diagram appears
in the on/off delay
symbol.
Содержание SmartRelay FL1A-H12RCE
Страница 1: ...IDEC SmartRelay Manual March 2001 www idec com ...
Страница 16: ...Getting to Know IDEC SmartRelay 1 6 IDEC SmartRelay User s Manual ...
Страница 32: ...Installing and Wiring IDEC SmartRelay 2 16 IDEC SmartRelay User s Manual ...
Страница 132: ...IDEC SmartRelay Functions 4 64 IDEC SmartRelay User s Manual ...
Страница 184: ...Applications 8 32 IDEC SmartRelay User s Manual ...
Страница 204: ...IDEC SmartRelay Menu Structure E 2 IDEC SmartRelay User s Manual ...
Страница 206: ...Type Numbers F 2 IDEC SmartRelay User s Manual ...
Страница 208: ...Abbreviations G 2 IDEC SmartRelay User s Manual ...