Technical Specifications
A-6
IDEC SmartRelay User’s Manual
A.3 Technical Specifications: FL1A-H12SND,
FL1A-H10RCA, FL1A-B10RCA
FL1A-H12SND
FL1A-H10RCA
FL1A-B10RCA
Power supply
Input voltage
24 V DC
24 V AC
Permissible Range
20.4 to 28.8 V DC
20.4 ... 26.4 V AC
Power consumption from
24 V DC
10 ... 20 mA
15 ... 120 mA
Voltage failure bridging
Typically 5 ms
Power loss at 24 V
0.2 ... 0.5 W
0.3 ... 1.8 W (AC)
Clock buffering at 25
_
C
Typically 80 h
Accuracy of the real-time
clock
Max.
”
5 s a day
Digital inputs
Number
8
6
Electrical isolation
No
No
Input voltage L+
•
Signal 0
•
Signal 1
< 5 V DC
> 8 V DC
< 5 V AC
> 12 V AC
Input current at
•
Signal 0
•
Signal 1
< 0.3 mA (I1...I6)
< 0.05 mA (I7, I8)
> 1.0 mA (I1...I6)
> 0.1 mA (I7, I8)
< 1.0 mA
> 2.5 mA
Delay time at
•
0 after 1
•
1 after 0
Typically 1.5 ms
Typically 1.5 ms
Typically 1.5 ms
Typically 15 ms
Line length (unshielded)
100 m
100 m
Analog inputs
Number
2 (I7, I8)
Range
0 ... 10 V DC
Digital outputs
Number
4
4
Содержание SmartRelay FL1A-H12RCE
Страница 1: ...IDEC SmartRelay Manual March 2001 www idec com ...
Страница 16: ...Getting to Know IDEC SmartRelay 1 6 IDEC SmartRelay User s Manual ...
Страница 32: ...Installing and Wiring IDEC SmartRelay 2 16 IDEC SmartRelay User s Manual ...
Страница 132: ...IDEC SmartRelay Functions 4 64 IDEC SmartRelay User s Manual ...
Страница 184: ...Applications 8 32 IDEC SmartRelay User s Manual ...
Страница 204: ...IDEC SmartRelay Menu Structure E 2 IDEC SmartRelay User s Manual ...
Страница 206: ...Type Numbers F 2 IDEC SmartRelay User s Manual ...
Страница 208: ...Abbreviations G 2 IDEC SmartRelay User s Manual ...