![IDEC OpenNet series Скачать руководство пользователя страница 324](http://html.mh-extra.com/html/idec/opennet-series/opennet-series_user-manual_617384324.webp)
24: R
EMOTE
I/O S
YSTEM
O
PEN
N
ET
C
ONTROLLER
U
SER
’
S
M
ANUAL
24-3
Data Communication between Remote I/O Master and Slave Stations
IDEC’s SX5S communication I/O terminals for INTERBUS can be used as slave stations in the remote I/O communica-
tion system. When the SX5S is used with the remote I/O master module, the input and output data at the slave station are
allocated to link registers in the
OpenNet Controller
CPU module as described below.
SX5S Communication I/O Terminals for INTERBUS
The following examples assume that the SX5S is connected at node 0.
Communication of 1-word Input Data (SX5S-SBN16S or SX5S-SBN16K)
Communication of 1-word Output Data (SX5S-SBR08)
Communication of 1-word Output Data (SX5S-SBT16K or SX5S-SBT16P)
Communication of 1-byte Input/Output Data (SX5S-SBM16K or SX5S-SBM16P)
Type No.
ID Code
Station Type
Data Length
SX5S-SBN16S
SX5S-SBN16K
02h
Remote Bus Station with Digital Inputs
1 word (16 inputs)
SX5S-SBR08
01h
Remote Bus Station with Digital Outputs
1 word (8 outputs)
SX5S-SBT16K
SX5S-SBT16P
01h
Remote Bus Station with Digital Outputs
1 word (16 outputs)
SX5S-SBM16K
SX5S-SBM16P
03h
Remote Bus Station with Digital I/Os
1 byte (8 in/8 out)
0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0
Master Station — Link Register (L1000)
Bit 15
8
7
0
Byte 1
Byte 0
OFF OFF OFF OFF OFF OFF OFF
ON
OFF OFF OFF OFF OFF OFF OFF OFF
Slave Station — Input (SX5S)
Input No. 7
0
15
8
= 0100h (256)
0 0 0 0 0 0 1 0
0 0 0 0 0 0 0 0
Master Station — Link Register (L1004)
Bit 15
8
7
0
Byte 1
Byte 0
OFF OFF OFF OFF OFF OFF
ON
OFF
Slave Station — Output (SX5S)
Input No. 7
0
= 0200h (512)
Low byte has no effect on the
8-point output slave station.
0 0 0 0 0 0 1 1
0 0 0 0 0 0 0 0
Master Station — Link Register (L1004)
Bit 15
8
7
0
Byte 1
Byte 0
OFF OFF OFF OFF OFF OFF
ON ON
OFF OFF OFF OFF OFF OFF OFF OFF
Slave Station — Output (SX5S)
Input No. 7
0
15
8
= 0300h (768)
0 0 0 0 0 1 0 0
–
–
–
–
–
–
–
–
Master Station — Link Register (L1000)
Bit 15
8
7
0
Byte 1
Byte 0
OFF OFF OFF OFF OFF
ON
OFF OFF
Slave Station — Input (SX5S)
Input No. 7
0
= 0400h (1024)
0 0 0 0 0 1 0 1
–
–
–
–
–
–
–
–
Master Station — Link Register (L1004)
Bit 15
8
7
0
Byte 1
Byte 0
OFF OFF OFF OFF OFF
ON
OFF
ON
Slave Station — Output (SX5S)
Input No. 7
0
= 0500h (1280)
Low byte is not used for
the 1-byte input data.
Low byte is not used for
the 1-byte output data.