8-point AC Input Module Specifications
Input Operating Range
The input operating range of the Type 1 (EN61131) input module is shown below:
Input Internal Circuit
Type No.
FC3A-N08A11
Rated Input Voltage
100 to 120V AC
Input Voltage Range
85 to 132V AC
Rated Input Current
8.3 mA/point (100V AC, 60 Hz)
Terminal Arrangement
See Terminal Arrangement char t on page 2-15.
Input Impedance
12 k
Ω
(60 Hz)
Turn ON Time (100V AC)
20 msec maximum
Turn OFF Time (100V AC)
20 msec maximum
Isolation
Between input terminals:
Not isolated
Internal circuit:
Photocoupler isolated
External Load for I/O Interconnection
Not needed
Signal Determination Method
Static
Effect of Improper Input Connection
If any input exceeding the rated value is applied, permanent damage may
be caused.
Cable Length
3m (9.84 ft.) in compliance with electromagnetic immunity
Connector on Mother Board
Screw Terminal Block
MSTBA2.5/20-G5.08
(Phoenix Contact)
Connector Insertion/Removal Durability
100 times minimum
Internal Current Draw
All inputs ON:
30 mA (24V DC)
All inputs OFF:
20 mA (24V DC)
Weight (approx.)
220g
Transition
OFF Area
Input V
oltage (V AC)
132
79
20
0
1.6
11
Input Current (mA)
ON Area
Area
8.3
6.5
100
COM
Inter
nal Cir
cuit
Input