![IDEC OpenNet series Скачать руководство пользователя страница 114](http://html.mh-extra.com/html/idec/opennet-series/opennet-series_user-manual_617384114.webp)
O
PEN
N
ET
C
ONTROLLER
U
SER
’
S
M
ANUAL
7-1
7: B
ASIC
I
NSTRUCTIONS
Introduction
This chapter describes programming of the basic instructions, available operands, and sample programs.
Basic Instruction List
Symbol
Name
Function
Words
AND
And
Series connection of NO contact
2
AND LOD
And Load
Series connection of circuit blocks
1
ANDN
And Not
Series connection of NC contact
2
BPP
Bit Pop
Restores the result of bit logical operation which was saved
temporarily
1
BPS
Bit Push
Saves the result of bit logical operation temporarily
1
BRD
Bit Read
Reads the result of bit logical operation which was saved tem-
porarily
1
CC=
Counter Comparison (=)
Equal to comparison of counter current value
3
CC
≥
Counter Comparison (
≥
)
Greater than or equal to comparison of counter current value
3
CDP
Dual Pulse Reversible Counter
Dual pulse reversible counter (0 to 65535)
3
CNT
Adding Counter
Adding counter (0 to 65535)
3
CUD
Up/Down Selection Reversible
Counter
Up/down selection reversible counter (0 to 65535)
3
DC=
Data Register Comparison (=)
Equal to comparison of data register value
3
DC
≥
Data Register Comparison (
≥
)
Greater than or equal to comparison of data register value
3
END
End
Ends a program
1
JEND
Jump End
Ends a jump instruction
1
JMP
Jump
Jumps a designated program area
1
LOD
Load
Stores intermediate results and reads contact status
2
LODN
Load Not
Stores intermediate results and reads inver ted contact status
2
MCR
Master Control Reset
Ends a master control
1
MCS
Master Control Set
Star ts a master control
1
OR
Or
Parallel connection of NO contacts
2
OR LOD
Or Load
Parallel connection of circuit blocks
1
ORN
Or Not
Parallel connection of NC contacts
2
OUT
Output
Outputs the result of bit logical operation
2
OUTN
Output Not
Outputs the inver ted result of bit logical operation
2
RST
Reset
Resets output, internal relay, shift register, or link register bit
2
SET
Set
Sets output, internal relay, shift register, or link register bit
2
SFR
Shift Register
For ward shift register
3
SFRN
Shift Register Not
Reverse shift register
3
SOTD
Single Output Down
Falling-edge differentiation output
1
SOTU
Single Output Up
Rising-edge differentiation output
1
TC=
Timer Comparison (=)
Equal to comparison of timer current value
3
TC
≥
Timer Comparison (
≥
)
Greater than or equal to comparison of timer current value
3
TIM
100-msec Timer
Subtracting 100-msec timer (0 to 6553.5 sec)
3
TMH
10-msec Timer
Subtracting 10-msec timer (0 to 655.35 sec)
3
TML
1-sec Timer
Subtracting 1-sec timer (0 to 65535 sec)
3
TMS
1-msec Timer
Subtracting 1-msec timer (0 to 65.535 sec)
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]