One safety-related input with two input channels with antivalent behavior (magnetic switch with NO
at S12 and NC at S13):
If the level at terminal S12 is logically 0 and the level at terminal S13 is logically 1, the safety-related
input is activated.
Timing diagram for one safety-related input with two input channels with antivalent behavior:
1 = Activation, transition to operating state Run: Outputs Energized
2 = Deactivation, transition to operating state Run: Outputs Deenergized (defined safe state)
Truth table for one safety-related input with two input channels with antivalent behavior:
Identical signal states are only permissible within the synchronization time
).
Otherwise, identical signal states trigger an alert.
The truth table applies to the wiring diagrams presented for the application functions.
If the magnetic switch in the wiring example above is used for guard monitoring, this means that
the magnetic switch is presented in the activated state and the guard is closed.
Consult the manual of the sensor/device you want to use for your application function for details
on signal state required for activation and deactivation as defined in the present document.
Signal State
at S12
Signal State
at S13
Activation State and Operating State
0
1
Safety-related input channel activated, operating state Run: Outputs
Energized
1
0
Safety-related input channel deactivated, operating state Run: Outputs
Deenergized
Содержание HR6S Series
Страница 1: ...http www idec com HR6S AB Safety Module Original instructions HR9Z B2190...
Страница 8: ...8 HR9Z B2190 8 2020...
Страница 14: ...14 HR9Z B2190 8 2020...
Страница 20: ...Introduction 20 HR9Z B2190 8 2020...
Страница 54: ...Installation 54 HR9Z B2190 8 2020...
Страница 80: ...Diagnostics 80 HR9Z B2190 8 2020...
Страница 86: ...Accessories Service Maintenance and Disposal 86 HR9Z B2190 8 2020...