Technical Data
HR9Z-B2190 8/2020
31
Data Functional Safety
Data Functional Safety
Characteristic
Value
Defined safe state
Safety-related outputs are de-energized
Normally Open: open
Normally Closed: closed
Maximum Performance Level (PL), Category
(as per ISO 13849-1:2015)
PL c, Category 1
Actual PL and category depend on wiring and
configuration.
Maximum Safety Integrity Level (SIL)
(as per IEC 61508-1:2010)
1
Actual SIL depends on wiring and configuration.
Safety Integrity Level Claim Limit (SILCL)
(as per IEC 62061:2005+AMD1:2012+AMD2:2015)
1
Actual SILCL depends on wiring and configuration.
Type
(as per IEC 61508-2)
B
Hardware Fault Tolerance (HFT)
(as per IEC 61508 and IEC 62061)
0
Stop Category for Emergency Stops
(as per ISO 13850 and IEC 60204-1)
0
Lifetime in years at an ambient temperature of 55 °C
(131 °F)
20
Safe Failure Fraction (SFF)
(as per IEC 61508 and IEC 62061)
>60 %
Probability of Dangerous Failure per hour (PFH
D
) in 1/h
(as per IEC 61508 and ISO 13849-1)
1175.6 x 10
-9
Mean Time To Dangerous Failure (MTTF
D
) in years
(high as per ISO 13849-1)
>30
Maximum number of cycles over lifetime
DC-13, 24 VDC 2 A: 50,000
AC-15, 250 VAC 3 A: 50,000
Содержание HR6S Series
Страница 1: ...http www idec com HR6S AB Safety Module Original instructions HR9Z B2190...
Страница 8: ...8 HR9Z B2190 8 2020...
Страница 14: ...14 HR9Z B2190 8 2020...
Страница 20: ...Introduction 20 HR9Z B2190 8 2020...
Страница 54: ...Installation 54 HR9Z B2190 8 2020...
Страница 80: ...Diagnostics 80 HR9Z B2190 8 2020...
Страница 86: ...Accessories Service Maintenance and Disposal 86 HR9Z B2190 8 2020...