UNCTIONS
2.
Select
Catch Input
in the Groups 1 through 4 pull-down list boxes. The Catch Input dialog box appears.
3.
Select
Catch Input Rising Edge
or
Catch Input Falling Edge
in the pull-down list.
Catching Rising Edge of Input Pulse
Catching Falling Edge of Input Pulse
Note:
When two or more pulses enter within one scan, subsequent pulses are ignored.
Example: Maintaining Catch Input
When a catch input is received, the catch input relay assigned to a catch input is turned on for only one scan. This example
demonstrates a program to maintain a catch input status for more than one scan.
Actual Input
ON
OFF
Catch Input Relay
ON
OFF
(M8090-M8095)
Note
END
Processed
1 scan time
Actual Input
ON
OFF
Catch Input Relay
ON
OFF
(M8090-M8095)
Note
END
Processed
1 scan time
Input I2 is designated as a catch input using the Function Area Settings.
When input I2 is turned on, special internal relay M8091 is turned on, and M0 is maintained in the self-
holding circuit.
When NC input M1 is turned off, the self-holding circuit is unlatched, and M0 is turned off.
M0 is used as an input condition for the subsequent program instructions.
M0
M8091
M0
M1
M0
Содержание FT1A-B12RA
Страница 1: ...FT9Y B1378 5 ...
Страница 2: ......
Страница 208: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 226: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 340: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 384: ...APPENDIX A 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 European Font ISO 8859 1 Cyrillic Font ANSI 1251 ...
Страница 385: ...SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 A 19 APPENDIX Japanese Font JIS X0201 ...
Страница 386: ...APPENDIX A 20 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...