12: R
EMOTE
I/O
12-2
S
MART
AXIS P
RO
/L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
Remote I/O Master
The SmartAXIS can be used as a remote I/O master by configuring the SmartAXIS as a remote I/O master in WindLDR. The
settings can be configured in the Function Area Settings dialog box of WindLDR.
The digital input information from the remote I/O slaves connected with connection 1 through 3 is input to I40 to I75, I80 to I115,
and I120 to I155. The analog input information from the remote I/O slaves is stored to D8149 to D8156, D8158 to D8165, and
D8167 to D8174.
The output information for Q40 to Q61, Q80 to Q101, and Q120 to Q141 on the remote I/O master is output from the remote I/O
slaves connected with connection 1 through 3. For details on data communication between the remote I/O master and the remote
I/O slaves, see "Remote I/O Communication Memory Refresh Image" on page 12-3.
Specifications
Item
Description
Connection 1
Digital inputs
I40 to I75
Digital outputs
Q40 to Q61
Analog inputs
D8149 (=AI10) to D8156 (=AI17)
Remote I/O slave 1 communication error status
D8148
Remote I/O slave 1 communication error
M8005
Remote host
IP address
000.000.000.000 to 255.255.255.255
Port number
0 to 65535
Timeout
100 ms to 25,500 ms (100 ms increments)
Connection 2
Digital inputs
I80 to I115
Digital outputs
Q80 to Q101
Analog inputs
D8158 (=AI20) to D8165 (=AI27)
Remote I/O slave 2 communication error status
D8157
Remote I/O slave 2 communication error
M8006
Remote host
IP address
000.000.000.000 to 255.255.255.255
Port number
0 to 65535
Timeout
100 ms to 25,500 ms (100 ms increments)
Connection 3
Digital inputs
I120 to I155
Digital outputs
Q120 to Q141
Analog inputs
D8167 (=AI30) to D8174 (=AI37)
Remote I/O slave 3 communication error status
D8166
Remote I/O slave 3 communication error
M8007
Remote host
IP address
000.000.000.000 to 255.255.255.255
Port number
0 to 65535
Timeout
100 ms to 25,500 ms (100 ms increments)
Refresh period
Communication processing
Scan asynchronous
Data update
Each scan end
Содержание FT1A-B12RA
Страница 1: ...FT9Y B1378 5 ...
Страница 2: ......
Страница 208: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 226: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 340: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 384: ...APPENDIX A 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 European Font ISO 8859 1 Cyrillic Font ANSI 1251 ...
Страница 385: ...SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 A 19 APPENDIX Japanese Font JIS X0201 ...
Страница 386: ...APPENDIX A 20 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...