S
MART
AXIS P
RO
/L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
5-23
5: S
PECIAL
F
UNCTIONS
Device allocation table
The devices used by the high-speed counter are as follows.
Special internal relay list
Special data register list
When using the devices above with instructions/FB where the data type unit can be specified, specify the data type as double word
(D). When the 32-bit data storage setting in the function area settings is set to
From Lower Word
, the lower word is stored in
the first device.
•
Start/stop high-speed counter
The high-speed counter can be started and stopped per group by turning the gate input on or off.
•
Current value storage locations
The current value for the single-phase high-speed counter is stored in special data registers as 2 words per group.
When the 32-bit data storage setting in the function area settings is set to
From Lower Word
, the lower word is stored in the
first device.
•
Comparison ON status
When the current value and the preset value match, the special internal relay turns on for only one scan.
Group
1
(I0 to I1)
2
(I2)
3
(I3 to I4)
4
(I5)
5
(I6)
6
(I7)
Read/Write
Comparison Output Reset
M8030
M8040
M8045
M8055
M8166
M8173
R/W
Gate Input
M8031
M8041
M8046
M8056
M8167
M8174
Reset Input
M8032
M8042
M8047
M8057
M8170
M8175
Reset Status
M8033
—
M8050
—
—
—
R
Comparison ON Status
M8034
M8043
M8051
M8060
M8171
M8176
Overflow
M8035
M8044
M8052
M8061
M8172
M8177
Underflow
M8036
—
M8053
—
—
—
Count Direction flag
M8037
—
M8054
—
—
—
Group
1
(I0 to I1)
2
(I2)
3
(I3 to I4)
4
(I5)
5
(I6)
6
(I7)
Read/Write
Current Value (Upper word)
D8050
D8056
D8062
D8068
D8134
D8140
R
Current Value (Lower word)
D8051
D8057
D8063
D8069
D8135
D8141
Preset Value (Upper word)
D8052
D8058
D8064
D8070
D8136
D8142
R/W
Preset Value (Lower word)
D8053
D8059
D8065
D8071
D8137
D8143
Reset Value (Upper word)
D8054
D8060
D8066
D8072
D8138
D8144
Reset Value (Lower word)
D8055
D8061
D8067
D8073
D8139
D8145
Group
1
(I0 to I1)
2
(I2)
3
(I3 to I4)
4
(I5)
5
(I6)
6
(I7)
Read/Write
Gate Input
M8031
M8041
M8046
M8056
M8167
M8174
R/W
Group
1
(I0 to I1)
2
(I2)
3
(I3 to I4)
4
(I5)
5
(I6)
6
(I7)
Read/Write
Current Value (Upper word)
D8050
D8056
D8062
D8068
D8134
D8140
R
Current Value (Lower word)
D8051
D8057
D8063
D8069
D8135
D8141
Group
1
(I0 to I1)
2
(I2)
3
(I3 to I4)
4
(I5)
5
(I6)
6
(I7)
Read/Write
Comparison ON Status
M8034
M8043
M8051
M8060
M8171
M8176
R
Содержание FT1A-B12RA
Страница 1: ...FT9Y B1378 5 ...
Страница 2: ......
Страница 208: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 226: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 340: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Страница 384: ...APPENDIX A 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 European Font ISO 8859 1 Cyrillic Font ANSI 1251 ...
Страница 385: ...SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 A 19 APPENDIX Japanese Font JIS X0201 ...
Страница 386: ...APPENDIX A 20 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...