28
Falcon GTS -
Installation & Servicing
INSTALLATION
43 SETTINGS (IF DHW SENSOR OPTION FITTED)
1.
Remove Screws and washers.
2.
Remove the top panel from the boiler.
3.
Loosen the top protection cover from the sides.
4.
Remove the PCB protection cover.
fal8546
4
3
fal8547
Access to DHW pump overrun adjustment potentiometers and the DHW load temperature limiter.
44 SETTING THE DHW PUMP OVERRUN AND LOAD TEMPERATURE LIMITER
Setting the DHW Pump Overrun
1.
The potentiometer on the PCB in the boiler is
used to adjust the DHW pump overrun.
The overrun can vary with an adjustment range
from 0 to 10 minutes (factory setting 4 min.)
Setting the Domestic Hot Water Load
Temperature Limiter
2.
The potentiometer on the P.C.B. in the boiler is
used to adjust the boiler temperature while
heating domestic hot water.
The load temperature setting can vary from 60
to 90
o
C (factory setting 75
o
C).
Reassembly
3.
At the end of the work, reassemble the P.C.B.
protection cover and the top panel, as for
access (Frame 43), but in the reverse order.
Note
.
Do not omit the serrated washers.
fal8548
1
2
INST
ALLA
TION