24
INSTALLATION
Esprit -
Installation and Servicing
esp8824
2
1
3
24 CONNECTING THE FLUE TO THE BOILER
Note.
Before fitting the flue turret fill the condensate trap within the
boiler by pouring a cupful of water into the flue outlet A.
Take care to ensure that the water is only poured into the flue
outlet, and does not spill into the boiler casing.
1.
Locate the flue into the turret.
2.
Insert the flue assembly through the prepared hole in the
wall. Push through and pull back to seal against outside
wall face.
3.
Locate the flue turret on the top of the boiler, ensuring that
the turret gasket is in place. Also ensure the turret is
located concentric with the flue aperture on the boiler top
panel. Check that the flue seal located in the top of the flue
manifold is secure and giving an effective seal.
4.
Secure the flue turret on top of the boiler by inserting the
open ends of the turret clamp under the 2 studs and fixing
it in the middle with the single M5 x 10mm pozi-hex screw
provided.
5. Flues over 1 metre long.
Fix the flue support bracket to the wall, using the 4 wall
plugs and wood screws.
NB.
The space bracket will utilise one fixing hole only
whilst used in conjunction with the stand-off option.
INST
ALLA
TION
203642-4.pmd
10/01/2008, 13:51
24