INSTALLATION
Harrier GT Range
- Installation
15
8.2 STANDARD CONTROL PANEL
8.2.1 Control panel presentation
8219-EN-5
1. Stop/Start switch for the burner.
2. STB test switch: momentary action to test the safety
thermostat.
3. Boiler thermostat first and second stage : graduated
from 30˚ to 90˚C. Integral pre-set stop limits the maximum
temperature to 80˚C. This stop can be adjusted if
necessary. To adjust it, remove the thermostat button by
pulling and use pliers to move the stop to the hole
according to the temperature desired. The second stage
thermostat must always be set to a lower value than the
first stage thermostat.
4. Boiler thermometer.
5. Location for possible smoke thermometer.
6. 5 AT fuse.
7. Safety thermostat
with manual reset (factory set at
100˚C).
8.2.3 Start up
- Put the boiler thermostat 3 on the desired position (alter
the stop position if necessary). Where a control unit is
fitted, see directions supplied with this control unit.
- Check that the safety thermostat 7 is not tripped. To do
this, unscrew the hexagonal cap and using a suitable
screw driver, press on the reset button.
- Put the burner switch 1 on run.
Important: in the absence of other settings, it is advised
never to set the boiler thermostat lower than mark 4 (40˚C) so
as to avoid all risk of condensation inside the boiler.
8.2.2 Operating principle of the control panel
Adjustment and regulation of the boiler is done by boiler
thermostats or by the adjustments on the external control
unit, if there is one. Operating safety is ensured by the
manual reset safety thermostat.