For the Protege controller and reader expander module, all RS485 and reader terminal connections must be
made using shielded grounded cable.
⦁
All readers must be connected with shielded, grounded cable.
⦁
A bell or visual indicator used as an arming acknowledgment signal must be listed to a UL security, signaling or
fire standard. If intended to be mounted outside, it must be rated for outdoor use.
⦁
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
⦁
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to UL10B or UL10C.
⦁
Must be installed with UL 1034 listed electronic locks for UL installations.
⦁
AC power on shall be indicated by an external panel mount LED (Lumex SSI-LXH312GD-150) and fitted into a
dedicated 4mm hole in the cabinet to provide external visibility. This shall be wired between 12V and a PGM
output that is programmed to follow the AC trouble input as shown below:
BZ
L1
D1
DO
LED
V+
V-
Z4
V-
Z3
Z2
V-
Z1
1K5 OHM
READER 1
INPUT 1-4
12VDC OUT
⦁
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
⦁
The power supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
Performance Levels
Destructive Attack
Line Security
Endurance
Standby Power
PRT-HRDM-DIN
Level I
Level I
Level IV
Level I
PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual
36