Outputs
The reader expander has 8 programmable outputs. These outputs are used to activate bell sirens, lighting circuits,
door locks, relay accessory products and other automation points.
Lock Outputs (1 and 2)
Relays are provided on outputs 1 and 2. These are used for the Lock 1 (Output 1 RD001:01) and Lock 2 (Output 2
RD001:02) functions and are used to control electric door strikes and other lock control devices.
Lock Output 1/2 Connection (Output 1 Shown):
Warning:
The relay outputs can switch to a maximum capacity of 7A. Exceeding this amount will damage the
output.
Standard Outputs (3 To 8)
The outputs 3, 4, 5, 6, 7 and 8 on the reader expander are open collector outputs and switch to a ground
connection.
The outputs have a default pre-programmed function as detailed in the following table and are used to control the
indicator and audible outputs on the attached reading device. These functions may be disabled by programming
the appropriate setting in the reader expander configuration.
Output Number
Description
RDxxx:03
LED 1 (Green) Reader 1
RDxxx:04
LED 2 (Red) Reader 1
RDxxx:05
Beeper Reader 1
RDxxx:06
LED 1 (Green) Reader 2
RDxxx:07
LED 2 (Red) Reader 2
RDxxx:08
Beeper Reader 2
PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual
21