55
9 Supplement
WIKA Operating Instructions - Process pressure transmitter IPT-2x
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 26: Behaviour in case of sudden change of the process variable. t
T
: dead time; t
A
: rise time; t
S
: jump response
time
1
Process variable
2
Output signal
IPT-2x
IPT-2x - IP68 (25 bar)
Dead time
≤ 25 ms
≤ 50 ms
Rise time (10 … 90 %)
≤ 55 ms
≤ 150 ms
Step response time (ti: 0 s, 10 … 90 %)
≤ 80 ms
≤ 200 ms
Damping (63 % of the input variable)
0 … 999 s, adjustable via menu item "
Damping
"
Reference conditions and influencing variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ
Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ
Relative humidity
45 … 75 %
Ʋ
Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)
Determination of characteristics
Limit point adjustment according to IEC 61298-2
Characteristic curve
Linear
Reference installation position
upright, diaphragm points downward
Influence of the installation position
Ʋ Piezoresistive/strain gauge measur
-
ing cell
depending on the process fitting and the chemical seal
Ʋ
Ceramic/metallic measuring cell
< 5 mbar/0.5 kPa (0.07 psig)
Deviation in the current output due to
strong, high-frequency electromagnetic
fields acc. to EN 61326-1
< ±150 µA
Deviation (according to IEC 60770-1)
Applies to the
digital
signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the
ana-
logue
current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio "nominal
measuring range/set span".